Multi Gas Detector

XP-3368II-W / XP-3368II / XP-3318II

Application

For daily check and safety in plants, tank, manhole, and tunnel construction

Features

  • Convert to 32 types gas’s concentration
  • Robust design
  • Wide range models
  • Up to five combustible gases can be set as target gas (option)
  • Selectable power supply: alkaline AA batteries/ rechargeable nickel metal hydride AA Batteries
  • Timer and stopwatch function

*Only for XP-3318II and XP-3368II-W

Specifications

Multi Gas Detector

ModelXP-3368II-WXP-3368IIXP-3318II
Target GasCombustible gas
/solvent vapor
OxygenCombustible gas
/solvent vapor
OxygenCombustible gas
/solvent vapor
Oxygen
Detection PrincipleCatalyticGalvanic cellCatalyticGalvanic cellCatalyticGalvanic cell
Mesuring Range
(Reference Indication)
0.0–100.0%LEL (100.1–110.0%LEL)
Enable to display in ppm.
0–25vol%
(25.1–50.0vol%)
0–5000ppm or
0–10000ppm
(5001–5500ppm or 10001–11000ppm)
0–25vol%
(25.1–50.0vol%)
0–100%LEL
(100.1–110.0%LEL)
0–25vol%
(25.1–50.0vol%)
Accuracy*2≤ 1000ppm : ±100ppm
1001ppm<n≤10000ppm : ±500ppm
Other than above: ±5%F.S.
±0.3vol%≤10%F.S. : ±2.5%F.S.
>10%F.S. : ±5%F.S.
±0.3vol%±5%F.S.±0.3vol%
Resolution0.1%LEL or 1ppm0.1vol%1ppm0.1vol%0.1%LEL0.1vol%
Alarm Set Value20%LEL18vol%250ppm or 500ppm18vol%20%LEL18vol%
Response TimeT90: 30 secondsT90 : 30 secondsT90 : 30 seconds
Continuous Operation Time*3Approx. 15 hours

Approvals

ATEX_logo CE_logo

Selectable Gases

Oxygen【O2】, Combustible gas