Fixed Gas Detector (Diffusion Type)
KD-12
Features
- Rugged, compact and lightweight.
- LED local display shows the gas concentration and alarm indication.
- Explosion-proof (ATEX, IECEx and TIIS approved).
- Water and dust-proof construction (IP65).
- All setup and maintenance can be performed easily on site by one person.
- The simple plug-in sensor module makes it easier.
- Infrared sensor for long-term stability and less calibration needs (KD-12R)
- SIL2 certified model is available (KD-12B-SIL).
- HART model is available (KD-12AH/BH).
Specifications
(KD-12 A/ B/ C)
Model | KD-12A | KD-12B | KD-12C |
Detection Principle | Hot wire semiconductor |
Catalytic combustion |
Thermal conductivity |
Gas Detected | Combustible gas, Toxic gas | Hydrogen, Helium, Carbon dioxide |
|
Sampling Method | Diffusion | ||
Detection Range | As per specifications | ||
Alarm Set Value | As per specifications | ||
Alarm Accuracy | Combustible gas: ±25% of alarm set value Toxic gas: ±30% of alarm set value |
||
Alarm Delay | Combustible gas: within 30s at 1.6 times of alarm set value Toxic gas: within 60s at 1.6 times of alarm set value |
||
Alarms | Gas alarm: Red LED lamp flashes Trouble alarm: Yellow LED lamp flashes (sensor trouble, power voltagemalfunction, etc.) |
||
Display | 4-digit digital LED display | ||
Output | Gas concentration analog signal ・4-20mADC (common to the negative side of power supply) Gas alarm contact (one stage only)*1 ・1a no-voltage contact output, Non-latching ・Rated load: 0.5A at 250VAC or 0.5A at 30VDC (resistance load) |
||
Operation | At 4 points of magnetic switches | ||
Approvals |
Ex d IIC T5 (TIIS)
II 2 G Ex db IIC T5 Gb (ATEX)
Ex db IIC T5 Gb (IECEx)
|
||
Degree of Protection | IP65 | ||
CE marked | Complied with CE Directive 2004/108/EC | ||
Applicable Cable | Cable out diameter: ø10-13mm 5-conductor cable*1: CVV-S 1.25mm23-conductor cable: CVV-S 2mm2 or 1.25mm2 |
||
Operating Temperature/Humidity*2 |
-10 to +50 °C 10 to 90 %RH (0 to 50 °C) |
||
Power Supply | 24 VDC (±20%) | ||
Power Consumption | 3W max. | ||
Dimensions | W158 x H116 x D68 mm (excluding protrusion) | ||
Weight | Approx. 1.2kg |
(KD-12 R /D /O)
Model | KD-12R | KD-12D | KD-12O | |
Detection Principle | NDIR (Non-dispersive infrared) |
Electrochemical cell | Galvanic cell | |
Gas Detected | Methane, Carbon dioxide |
Carbon monoxide |
Hydrogen sulfide |
Oxygen |
Sampling Method | Diffusion type | |||
Detection Range | As per specifications | 0 to 100 ppm, 0 to 150 ppm, or 0 to 250 ppm*3 |
0 to 30 ppm or 0 to 50 ppm*3 |
0 to 25.0 vol% |
Alarm Set Value | As per specifications | FS100ppm: 25ppm (recommendation) FS150/250ppm: 50ppm (recommendation) |
10ppm | 18.0vol% |
Alarm Accuracy | ±25% of alarm set value | ±30% of alarm set value | ±1.0vol% of alarm set value |
|
Alarm Delay | Within 30s at 1.6
times of alarm set value |
Within 60 s at 1.6 times of alarm set value |
Within 5s to reach 18vol% under conditionof 10vol%*4 |
|
Alarms | Gas alarm: Red LED lamp flashes Trouble alarm: Yellow LED lamp flashes (sensor trouble, power voltage malfunction,etc.) |
|||
Display | 4-digit digital LED display | |||
Output | Gas concentration analog signal ・4-20mADC (common to the negative side of power supply) Gas alarm contact (one stage only)*1 ・1a no-voltage contact output, Non-latching ・Rated load: 0.5A at 250VAC or 0.5A at 30VDC (resistance load) |
|||
Operation | At 4 points of magnetic switches | |||
Approvals | Ex d IIB T5 (TIIS) II 2 G Ex db IIC T5 Gb (ATEX) Ex db IIC T5 Gb (IECEx) |
|||
Degree of Protection | IP65 | |||
CE marked | Complied with CE Directive 2004/108/EC | |||
Applicable Cable | Cable out diameter: ø10-13mm 5-conductor cable*1: CVV-S 1.25mm23-conductor cable: CVV-S 2mm2 or 1.25mm2 |
|||
Operating Temperature/Humidity*2 |
-10 to +50 °C
10 to 90 %RH (0 to 50 °C) |
-10 to +40 °C 30 to 85 %RH |
0 to +40 °C 30 to 85 %RH |
|
Power Supply | 24VDC (±20%) | |||
Power Consumption | 2.2W max. | 1.2W max. | ||
Dimensions | W158 x H120 x D68 mm (excluding protrusion) | |||
Weight | Approx. 1.3kg |
(KD-12B-SIL)
Model | KD-12B-SIL |
Detection Principle | Catalytic combustion |
Gas Detected | Combustible gas, Toxic gas |
Sampling Method | Diffusion |
Detection Range | As per specifications |
Alarm Set Value | As per specifications |
Alarm Accuracy | Combustible gas: ±25% of alarm set value Toxic gas: ±30% of alarm set value |
Alarm Delay | Combustible gas: within 30s at 1.6 times of alarm set value Toxic gas: within 60s at 1.6 times of alarm set value |
Alarms | Gas alarm: Red LED lamp flashes Trouble alarm: Yellow LED lamp flashes (sensor trouble, power voltagemalfunction etc.) |
Output | Gas concentration analog signal ・4-20mADC (common to the negative side of power supply) Gas alarm contact (one stage only)*1 ・1a no-voltage contact output, Non-latching ・Rated load: 0.5A at 250VAC or 0.5A at 30VDC (resistance load) |
Display | 4-digit digital LED display |
Operation | At 4 points of magnetic switches |
Approvals | Ex d IIC T5 (TIIS)
II 2 G Ex db IIC T5 Gb (ATEX)
Ex db IIC T5 Gb (IECEx)
|
Degree of Protection | IP65 |
Functional Safety | ・SIL2 capable ・Hardware Fault Tolerance: zero (0) ・Applicable standards: IEC 61508-2, EN 61508-2 and JIS C 0508-2 |
Applicable Cabel | Cable out diameter: ø10-13mm 5-conductor cable*1: CVV-S 1.25mm2 3-conductor cable: CVV-S 2mm2 or 1.25mm2 |
Operation Temperature /Humidity |
-10 to+50 °C 10 to 90 %RH (0 to 50 °C) |
Power Supply | 24 VDC (±20%) |
Power Consumption | 3W max. |
Dimensions | W158 x H116 x D68 mm (excluding protrusion) |
Weight | Approx. 1.2kg |
(KD-12AH/BH)
Model | KD-12AH | KD-12BH |
Detection Principle | Hot wire semiconductor | Catalytic combustion |
Gas Detected | Combustible gas | |
Sampling Method | Diffusion | |
Detection Range | As per specifications | |
Alarm Set Value | As per specifications | |
Alarm Accuracy | ±25% of alarm set value | |
Alarm Delay | Within 30s at 1.6 times of alarm set value | |
Alarms | Gas alarm: Red LED lamp flashes Trouble alarm: Yellow LED lamp flashes (sensor trouble, power voltagemalfunction, etc.) |
|
Display | 4-digit digital LED display | |
Output | Gas concentration analog signal and HART signal ・4-20mADC(common negarive with power supply) ・Wired HART signal (superimposed over 4-20mA signal), Protocol Rev. 7.5 Gas alarm contact (1st stage only)*1 ・1a non-voltage, Latching (standard) or non-latching |
|
Approvals |
II 2 G Ex db IIC T5 Gb (ATEX)
Ex db IIC T5 Gb (IECEx)
|
|
Degree of Protection | IP65 | |
CE marked | Complied with CE Directive 2004/108/EC | |
Applicable Cable | Cable out diameter: ø10-13mm 5-conductor cable*1: CVV-S 1.25mm23-conductor cable: CVV-S 2mm2 or 1.25mm2 |
|
Operating Temperature/Humidity*2 | -10 to +50 °C 10 to 90 %RH (0 to 50 °C) |
|
Power Supply | 24 VDC (±20%) | |
Power Consumption | 3W max. | |
Dimensions | W127 x H116 x D68 mm (excluding protrusion) | |
Weight | Approx. 1.2kg |
*1 Screwless type only
*2 No radical temperature or humidity changes and no condensing
*3 Specify when purchasing
*4 Under the condition of 20 ±2 C°
Approvals
Connectable Alarm Units
UV-810 (Multi Point), V3 Series, NV-120 Series